Описание товара
Подробности
Professional Automation Control System for CAEN Automation System Enclosures
- 2-Series engine | Dual-bus architecture
- 4GB Compact Flash memory card slot
- Built-in Cresnet distribution and hub/repeater
- 10/100 Ethernet capable | SSL encryption
- e-Control 2 and RoomView enabled
- SNMP support | Built-in firewall, NAT and router
- 8 Versiport I/O ports & 8 relay ports built-in
- 2 Y-Bus / 1 Z-Bus control card expansion slots
- Internal power supply | CAEN enclosure installation
- Configurable via Crestron D3 Pro software
Дополнительная информация
Processor | ||
CPU | 32-bit Freescale ColdFire® Microprocessor | |
Memory | ||
SDRAM | 64 MB | |
NVRAM | 256 KB | |
Flash | 4 MB | |
Compact Flash | expandable up to 4 GB (not included) | |
Operating System | ||
Real-time, preemptive multi-threaded/multitasking kernel; FAT32 file system with long names; supports SIMPL™ Windows® and SIMPL+® | ||
Ethernet | ||
With C2ENET-1 | 10/100BaseT, auto-negotiating, full/half duplex, static IP or DHCP/DNS, SSL, TCP/IP, UDP/IP, CIP, SMTP, SNMP, built-in Web server and e-mail client; supports Crestron e-Control®2 XPanel and RoomView™ applications | |
With C2ENET-2 | All above features plus: built-in firewall, router, and network address translator (NAT) | |
Y-Bus Connectors & Expansion Slots | ||
40 Mb/s parallel communications; Internal backplane for integrated control ports and Y-Bus expansion slots | ||
I/O 1 - 8 | (1) 9-pin 3.5mm detachable terminal block comprising (8) “Versiports” – digital input/output or analog input ports; Digital Input: Rated for 0-24 Volts DC; input impedance 20k ohms; logic threshold 1.24 Volts DC; Digital Output: 250 mA sink from maximum 24 Volts DC; catch diodes for use with “real world” loads; Analog Input: Rated for 0-10 Volts DC, protected to 24 Volts DC maximum; input impedance 20k ohms; Programmable 5 Volts, 2k ohms pull-up resistor per pin; All ports referenced to ground | |
RELAY OUTPUT 1 - 8 | (2) 8-pin 3.5mm detachable terminal blocks comprising (8) normally open, isolated relays; Rated 1 Amp, 30 Volts AC/DC; MOV arc suppression across contacts | |
S1, S2 | (2) Y-Bus expansion slots; Accept all Y-Bus control cards | |
Z-Bus Expansion Slots | ||
300 Mb/s parallel communications; Backplane for Z-Bus expansion slots | ||
S-3 Z-BUS | (1) Z-Bus expansion slot; Accepts all Z-Bus control cards | |
Additional Connectors | ||
LEFT, RIGHT | (2) 5-pin 0.156 inch headers; Module interconnect ports, connect to CLX-Series lighting control modules using interconnect cables provided | |
Cresnet Hub/Repeater | Cresnet data and power distribution: NET A – H: (32) 4-pin 3.5mm detachable terminal blocks comprising (4) Cresnet ports (paralleled) per each of (8) segments POWER 1 – 4: (4) 3-pin 3.5mm detachable terminal blocks comprising (1) Cresnet power selection connector per each of (4) power groups; | |
OVERRIDE | (1) 3-pin 3.5mm detachable terminal block comprising (2) inputs from external contact closures to trigger the preset Override state in CLX-Series modules connected to the module interconnect ports; Maximum Input: 10mA at 5 Volts | |
BACKUP NET INPUT | (1) 4-pin 3.5mm detachable terminal block Backup Cresnet port; Connects to the NET port of a backup control system and power supply | |
FAULT | (1) 2-pin 3.5mm detachable terminal block; Contact closure output; Relay closed when PAC2 becomes inactive; Connects to digital input of backup control system | |
NET | (1) 4-pin 5mm detachable terminal block; Cresnet port, Master/Slave selectable; Expandable via C2N-NPA8 Network Poll Accelerator | |
COMPUTER | (2) DB9 female; RS-232 computer console port | |
Line Power | (1) Attached input power cable (~1 ft long) with inline IEC320 socket; Connects to AC power source using grounded pigtail cable and DIN rail terminal block (both included) | |
Reset Buttons | ||
HW-R | Hardware reset (reboots the control system) | |
SW-R | Software reset (restarts the SIMPL program) | |
LED Indicators | ||
NET A – H | (yellow x8) Indicate Cresnet communications on each respective segment | |
POWER 1 – 4 | (green x4) Indicate 24 Volts DC power present at each respective power group | |
PWR | (green) Indicates power supplied to unit via AC line or BACKUP NET INPUT | |
NET | (yellow) Indicates Cresnet bus activity | |
MSG | (red) Indicates control system has generated an error message | |
LNK A | (red) Indicates a valid connection on LAN port A | |
ACT A | (red) Indicates activity on LAN port A | |
LNK B | (red) Indicates a valid connection on LAN port B | |
ACT B | (red) Indicates activity on LAN port B | |
FAULT | (red) Indicates PAC2 has become inactive, FAULT output is active (relay closed) | |
Power Requirements | ||
Main Power Consumption | 2.4 Amps, 100-250 Volts AC, 50/60 Hz | |
Available Cresnet Power | 50 Watts (shared with control card expansion slots) | |
Environmental | ||
Temperature | 41° to 113°F (5° to 45°C) | |
Humidity | 10% to 90% RH (non-condensing) | |
Enclosure | ||
Black and gray metal, surface mount box with (2) integral mounting flanges; Occupies 1 module space in a single-width CAEN or CAENIB enclosure, or 2 side-by-side module spaces in a double-width enclosure | ||
Dimensions | ||
Height | 8.00 in (20.32 cm) | |
Width | 14.00 in (35.56 cm) | |
Depth | 3.75 in (9.52 cm) | |
Weight | ||
8.0 lb (3.62 kg) – with line cord |