300 Watt Cresnet Power Supply. Cresnet Power Supply, 300 watt
Дополнительная информация
Load Ratings | ||
Per Channel | 75 Watts (3.125 Amps) @ 24 Volts DC regulated | |
System Total | 300 Watts (12.5 Amps) @ 24 Volts DC regulated | |
Ripple / Noise | <150 mV | |
Load Protection | Electronic circuit breaker per channel, each rated at 75 watts nominal / 100 watts maximum; 4 Amp, 125V internal fuse; all channels shut off in case of total system overload | |
Sequential Startup | Outputs activate sequentially when power supply system is enabled (see PWR ON, PWR OFF/SLAVE control) | |
Power Requirements | ||
4 Amps, 100-240 Volts AC, 50/60 Hz | ||
Connections | ||
1 – 8 | (16) 4-pin 5mm detachable terminal blocks comprising (2) paralleled Cresnet ports per each of (8) output channels; 24 Volt DC power outputs with Cresnet data pass-thru from NET port | |
NET | (1) 4-pin 5mm detachable terminal block; Ordinarily connects to the Master Cresnet port of a control system; Cresnet data ‘Y’ and ‘Z’ terminals pass through to ports 1 – 8; Applying 24 Volts DC to the ‘24’ and ‘G’ terminals enables the power supply system when in “SLAVE” mode | |
AC Line | (1) attached input power cable (~1 ft long) with inline IEC320 socket; Connects to grounded AC power source using 3-prong power cable or pigtail cable, both provided | |
Controls | ||
PWR ON, PWR OFF/SLAVE | (1) rocker switch; enables/disables the power supply system if no external DC voltage is applied to the NET port, or selects “SLAVE” mode to allow enabling the power supply system remotely by applying an external 24V DC signal to the NET port | |
RESET 1 – 8 | (8) miniature pushbuttons; each resets its respective output channel, or momentarily disables the channel while held | |
SYSTEM RESET | (1) miniature pushbutton; resets all output channels sequentially, or momentarily disables all channels while held | |
SETUP | (1) miniature pushbutton; used for touch-settable ID (TSID) | |
LED Indicators | ||
PWR 1 – 8 | (green) Indicate 24V DC power present at each channel output | |
OVRLD 1 – 8 | (red) Indicate a load in excess of 75 watts on a given channel, channel output disabled | |
SYSTEM OVRLD | (red) Indicates a total load in excess of 300 watts on the power supply system, all channels disabled | |
PWR | (green) Indicates power supply system is enabled | |
NET | (yellow) Indicates communication with Cresnet system | |
SETUP | (red) Used for touch-settable ID (TSID) | |
Environmental | ||
Temperature | 41° to 104°F (5° to 40°C) | |
Humidity | 10% to 90% RH (non-condensing) | |
Enclosure | ||
Chassis | Aluminum, black anodized with polycarbonate label overlay, convection-cooled, vented top and sides | |
Mounting | Surface mount using (2) integral mounting flanges, or 3U 19-inch rack-mountable (C2N-RMAK rack kit sold separately) | |
CAEN Automation Enclosure | Occupies 1 module space in a single-width enclosure, or 2 side-by-side module spaces in a double-width enclosure (CAEN-MK mounting kit sold separately) | |
Dimensions | ||
Height | 5.19 in (13.18 cm) | |
Width | 13.25 in (33.66 cm) | |
Depth | 3.29 in (8.36 cm) | |
Weight | ||
5.3 lb (2.4 kg) |