Описание товара
Подробности
The GLS-PLS-120/277 is a 3-Phase Power Loss Sensor designed for use with Crestron Green Light™ systems to activate Override mode during a power failure. In response to a signal from the GLS-PLS-120/277, the lighting system program can be temporarily overridden while designated emergency lighting circuits are changed to their override preset levels and unnecessary lighting and other devices are shut down to minimize the demand on emergency power equipment.
- Senses loss of power on each leg of a 3-phase feed
- Used to satisfy UL 924 (Emergency Power Equipment) requirements
- Works with 120 or 277 Volt feeds
Дополнительная информация
Input Voltages | ||
277V Voltage Range | 235 to 305 Volts AC, 50/60 Hz | |
120V Voltage Range | 102 to 132 Volts AC, 50/60 Hz | |
Connections | ||
Ground | (1) #6-32 Ground stud | |
PHASE A | (2) captive screw terminals; Main feed Phase A sensing input, 277 or 120 Volts; Wire Size: 30 to 10 AWG (0.05 to 6.0 mm2) | |
PHASE B | (2) captive screw terminals; Main feed Phase B sensing input, 277 or 120 Volts; Wire Size: 30 to 10 AWG (0.05 to 6.0 mm2) | |
PHASE C | (2) captive screw terminals; Main feed Phase C sensing input, 277 or 120 Volts; Wire Size: 30 to 10 AWG (0.05 to 6.0 mm2) | |
N | (1) captive screw terminal, main feed neutral; Wire Size: 30 to 10 AWG (0.05 to 6.0 mm2) | |
OUTPUT 1 – 2 | (2) sets of (2) captive screw terminals comprising (2) Form ‘A’ contact closures, electrically isolated; Both outputs close when main feed power is removed from any phase sensing input; Contact Closure Rating: 1 Amp @ 24 Volts DC; Wire Size: 30 to 12 AWG (0.05 to 4.0 mm2) | |
Indicators & Controls | ||
NORMAL A – C | (3) Green LEDs, each illuminates when corresponding test switch is set to NORMAL and power is present at corresponding phase sensing input | |
TEST A – C | (3) Red LEDs, each illuminates when corresponding test switch is set to TEST and power is present at corresponding phase sensing input | |
Test Switches | (3) Slide switches behind cover plate, used to set each corresponding phase sensing input to TEST mode | |
Enclosure | ||
Galvanized steel with polycarbonate label overlay; surface mount with integral mounting flanges top and bottom; 3/4” & 1/2" conduit knockouts top, bottom, and both sides | ||
Environmental | ||
Temperature | 32° to 104°F (0° to 40°C) | |
Humidity | 0% to 95% RH (non-condensing) | |
Heat Dissipation | 51 BTU/Hr | |
Dimensions | ||
Height | 12.69 in (32.23 cm) | |
Width | 5.19 in (12.75 cm) | |
Depth | 2.82 in (7.14 cm) | |
Weight | ||
3.7 lb (1.7 kg) |